Chapter 2 gave you Ohm's law and power. This chapter puts those tools to work on the kinds of circuits electricians actually build — and on voltage drop, a dedicated scoring area on Utah's Journeyman exam.

3.1 Series Circuits in the Field

True pure-series power wiring is uncommon for outlets (we parallel loads so each sees full voltage), but series thinking shows up everywhere:

Rules to keep sharp:

3.2 Parallel Circuits in the Field

Branch-circuit loads are almost always in parallel across the same voltage.

Rules:

Example. On a 120 V circuit, three loads draw 2 A, 3 A, and 5 A.

[ I_T = 10 A,R_{eq} = = 12  ]

3.3 Multiwire Branch Circuits

A common residential/commercial arrangement uses two ungrounded ("hot") conductors with opposite legs / phases and a shared neutral (grounded conductor).

On a 120/240 V single-phase system:

If both hots are on the same leg (miswired), the neutral can carry the sum — a serious overload risk. Handle-tied or common-trip breakers, correct phasing, and identifying neutrals matter.

Exam theme: neutrals are current-carrying conductors in normal operation. Do not confuse them with equipment grounding conductors.

3.4 Introduction to AC Waveforms

AC voltage and current vary with time, typically as a sine wave at 60 Hz in the U.S.

Important values:

For a sine wave:

[ E_{RMS} = 0.707 E_{peak} ]

[ E_{peak} = 1.414 E_{RMS} ]

When someone says "120 volts," they almost always mean 120 V RMS. Meters used for power work display RMS for sine waves (true-RMS meters needed for distorted waveforms).

3.5 Frequency, Period, and Wavelength (Light Touch)

[ f = ]

At 60 Hz, the period (T) is 1/60 second. You rarely calculate this on the electrician exam, but transformers, motors, and capacitive/inductive behavior all assume the system frequency.

3.6 Resistance, Inductance, and Capacitance

Real AC circuits contain more than resistance.

Property Symbol Opposes / stores Phase note
Resistance (R) Dissipates energy as heat V and I in phase
Inductance (L) (henry) Opposes change in current Current lags voltage
Capacitance (C) (farad) Opposes change in voltage Current leads voltage

Inductive reactance:

[ X_L = 2f L ]

Capacitive reactance:

[ X_C = ]

Impedance (Z) is the AC equivalent of resistance for Ohm's law:

[ E = I Z ]

For a series R–L–C type relationship (magnitudes):

[ Z = ]

3.6.1 Power factor

[ PF = = = ]

Example. A load draws 10 A at 240 V. Metered true power is 1920 W.

[ VA = 240 = 2400,PF = 1920/2400 = 0.8 ]

3.7 Transformers (Theory You Need)

Transformers change AC voltage using magnetic coupling. Ideal approximate relationships:

[ = = ]

Power in ≈ power out (ignoring losses):

[ E_P I_P E_S I_S ]

Example. 480 V primary, 120 V secondary, secondary load 10 A. Approximate primary current:

[ I_P = 2.5 A ]

Utah's practical exam includes transformer termination for unlimited electrician candidates — matching conductors to correct points on a Delta-Wye transformer. Theory here supports that hands-on task: know high/low voltage sides, neutral/X0 where applicable, and that wrong landing points create dangerous voltages.

3.7.1 Separately derived systems

A transformer with no direct electrical connection between primary and secondary is a classic separately derived system. It needs its own grounding/bonding treatment under Article 250 — foreshadowing Chapter 6.

3.8 Voltage Drop: Why It Matters

Voltage drop is the reduction in voltage from source to load caused by conductor resistance (and, more completely, impedance). Excessive drop causes:

The NEC informational notes recommend (not always a mandatory "shall") limiting drop to roughly:

Exam questions may ask you to calculate drop, or to size wire so drop stays under a stated percentage. Read carefully whether the question uses one-way length or round-trip.

3.9 Voltage Drop Formulas

3.9.1 Single-phase (most common exam form)

[ VD = ]

Where:

3.9.2 Three-phase

[ VD = ]

(Uses () instead of 2 for balanced three-phase line conductors.)

3.9.3 Percent voltage drop

[ %VD = ]

3.9.4 Finding required CM for a maximum drop

Rearrange single-phase:

[ CM = ]

Then choose the next larger standard conductor size from NEC Chapter 9 Table 8 (or Ugly's).

3.10 Worked Voltage Drop Problems

Problem A. A 120 V single-phase branch circuit supplies 16 A. One-way length is 90 ft. Conductor is 12 AWG copper (6530 cmil). Use (K = 12.9).

[ VD =  V ]

[ %VD = % ]

That exceeds a 3% branch-circuit design target — you might upsize the wire.

Problem B. Same load and length, but 10 AWG copper (10380 cmil):

[ VD =  V % ]

Problem C. 208 V three-phase feeder, 40 A, 200 ft one-way, 1 AWG copper (83690 cmil), (K = 12.9):

[ VD =  V ]

[ %VD = % ]

Problem D. What minimum CM is needed for 240 V single-phase, 30 A, 150 ft, max 3% drop, copper (K=12.9)?

[ VD_{max} = 0.03 = 7.2 V ]

[ CM = = 16125  ]

6 AWG copper is 26240 cmil; 8 AWG is 16510 cmil — 8 AWG is just enough by this math (always confirm ampacity and termination temperature ratings too; voltage drop never overrides ampacity rules).

3.11 Using Tables Instead of (K)

Ugly's and many exam prep sheets also provide voltage drop tables or ohms-per-1000-feet methods:

[ VD = I R ]

for single-phase, where (R) is ohms per 1000 ft from the conductor table at the appropriate temperature. Same idea, different packaging. Use whichever form matches the given data.

3.12 Skin Effect and AC Resistance (Awareness)

At larger sizes and AC, effective resistance rises slightly versus DC (skin effect). Precision design may use AC impedance tables. For typical branch-circuit exam problems, the standard (K) method is what you will use.

3.13 Troubleshooting With Voltage Drop Thinking

If voltage at a panel is fine but voltage at a load is low:

  1. Measure under load (drop appears when current flows).
  2. Check conductor size and length.
  3. Check for loose neutrals/hots (connection resistance adds drop and heat).
  4. Check shared neutrals and overloaded multiwire circuits.
  5. Check for undersized extension cords or temporary wiring.

3.14 Practice Problems

  1. Series: 10 Ω and 30 Ω on 120 V. Find current and voltage across the 30 Ω resistor.
  2. Parallel: loads of 4 A and 12 A on 120 V. Find total current and equivalent resistance.
  3. A load is 1800 VA at 120 V, PF 0.75. Find current and true power.
  4. Single-phase VD: 20 A, 120 ft one-way, 10 AWG Cu (10380 cmil), (K=12.9), 120 V system. Find volts dropped and %VD.
  5. What CM is required for 3% max drop: 240 V, 50 A, 180 ft, single-phase copper, (K=12.9)?
  6. Transformer: 480 V to 240 V, secondary delivers 25 A. Approximate primary current (ignore losses).

3.14.1 Answers

  1. (R_T=40) Ω, (I=3) A, (V_{30}=90) V.
  2. (I_T=16) A, (R_{eq}=7.5) Ω.
  3. (I = 1800/120 = 15) A; (P = 1800 = 1350) W.
  4. (VD = (2)/10380 ) V; (%VD %).
  5. (VD_{max}=7.2) V; (CM=(2)/7.2 = 32250) cmil → next standard size at least 4 AWG (41740 cmil) after checking ampacity.
  6. (I_P (240)/480 = 12.5) A.

3.15 Looking Ahead

You can now quantify how wire size and length steal voltage from a load. Chapter 4 turns to the hardware itself: conductor types, ampacity, cables, raceways, and enclosures — the Code side of getting current from the panel to the load without cooking the insulation.